MBF COMPANY CONFIDENTIAL FIELD INFORMATION BULLETIN SERVICE GROUP(S): MICRO,MINI,LARGE MFG: ALL NACS TYPE(S): N046 MFG. MODEL(S): AC LINE CONDITIONERS CATEGORY: PREVENTIVE MAINT. DESC: UPS, POWER CONDITIONERS *** TABLE OF CONTENTS AS OF 12/20/90 *** FIB 00001.AC Power Line Conditioners..................................08/14/89 FIB 00002.Stand-By UPS (Uninterruptable Power Source).................09/07/89 PREVENTIVE MAINT.-ALL-AC LINE CONDITIONERS----------Table Of Contents Pg01 of 01 FIB 00001 08/14/89 *** AC Power Line Conditioners *** FREQUENCY: EVERY SIX MONTHS ITEM RECOMMENDED ACTION |----------------------|. |----------------------------------------------| BASE Clean and observe for any physical damage TEST Test using ECOS 7106. All normally run tests should pass with the following exceptions: TEST 3 (Neutral to Ground short test) - should indicate a Neutral-to-ground short TEST 10 (Isolated Ground Receptacle test) - This test is not applicable. ORIGINATOR: N. Jones PREVENTIVE MAINT.-ALL-AC LINE CONDITIONERS----------FIB001 Pg001 FIB 00002 09/07/89 *** Stand-By UPS (Uninterruptable Power Source) *** FREQUENCY: EVERY TWO MONTHS ITEM RECOMMENDED ACTION |----------------------! |----------------------------------------------| BASE Clean and observe for physical damage. Check fan operation. OPERATION Disconnect the input AC voltage (with the attached system running BUT NOT IN ANY CUSTOMER PROGRAMS!) and insure inverter operation is normal and AC is maintained for five minutes. If the AC is not maintained, the batteries will have to be replaced. The cost of battery replacement is a customer responsibility and is not covered in the maintenance agreement on the UPS. Refer to FIB 4 in the LINE CONDITIONER-ALL FIB group for battery replacement procedures and cautions. MKT Code Description Cost . -------- ------------------------------ ---- ZA050 UPS Replacement Batteries $300 (includes installation) ORIGINATOR: N. Jones PREVENTIVE MAINT.-ALL-AC LINE CONDITIONERS----------FIB002 Pg001